Emergency & Exit Lighting: The OBC and CEC Requirements That Get Buildings Rejected

Floor plan: corridor with an emergency lighting unit, remote heads, directional exit signs and the path of egress to the stair and the exterior exit

"The exit signs are installed." Great. But are they on a transfer switch? Do the battery units provide 30 minutes or 120 minutes? Is the illumination at floor level actually 10 lux? These are the questions building inspectors ask - and the ones that delay occupancy permits when the answers are wrong.

Two Codes, One System

Emergency lighting in Ontario is designed to two separate codes that must be satisfied simultaneously; testing falls under the Ontario Fire Code:

Code Governs Key Sections
Ontario Building Code (OBC)Where emergency lighting is required, illumination levels, exit sign placementOBC 3.2.7.3 (Emergency Lighting), 3.2.7.4 (Emergency Power for Lighting), 3.4.5 (Exit Signs)
Canadian Electrical Code (CEC), adopted in Ontario as the OESCHow the system is wired, power sources, transfer requirementsCEC Section 46 (Emergency Power), Rule 46-400

Where Is Emergency Lighting Required? (OBC 3.2.7.3)

  • All exit corridors, stairwells, and passageways
  • Principal routes providing access to exit from open floor areas
  • All underground walkways and pedestrian tunnels
  • Rooms with occupant loads of 60 or more (assembly areas)
  • Principal routes to exits in service rooms, such as electrical rooms
  • Elevator cars (required by CSA B44, not the OBC)

Illumination Requirements

Location Average Illumination (min. 1 lux) Measurement Point
Exit corridors & stairways10 luxAt floor level
Open floor areas (principal routes)10 luxAt floor level along the route
Elevator carsPer CSA B44Elevator code (TSSA)
The 10 lux average must be maintained at the end of the battery duration period - not at full charge. Battery units dim as they discharge. Designers must account for lumen depreciation and ensure 10 lux at the 30-minute (or 1-hour or 2-hour) mark.

Battery Duration: 30 Minutes, 1 Hour, and 2 Hours

Building Type Required Duration Reason
Other buildings not listed for longer duration30 minutesMinimum duration under OBC 3.2.7.4 for many standard applications
Certain Group B and other listed buildings1 hourConfirm occupancy and building classification under OBC 3.2.7.4
High buildings in the scope of OBC 3.2.62 hoursExtended evacuation and life-safety operation time
Generator-backed emergency lightingPer OBC/NBC and CSA C282Duration, transfer, fuel supply, and testing depend on building classification and generator standard requirements

Exit Sign Requirements (OBC 3.4.5)

  • Green pictogram exit signs (running man symbol, ISO 7010) are required in new construction - red "EXIT" text signs do not comply
  • Must be visible on approach to the exit (OBC 3.4.5.1)
  • Directional arrow signs where no exit is visible
  • Must be continuously illuminated - internally, externally or photoluminescent (CAN/ULC-S572)
  • Must have integral battery backup or be on emergency power circuit

CEC Section 46 - Emergency Power Supply

CEC Section 46 governs emergency power supplies, unit equipment and exit sign wiring:

CEC Rule Requirement
46-108Emergency system wiring shall be kept entirely independent of all other wiring - it may share an enclosure only in transfer switches and in exit signs and emergency lights supplied from two sources (Subrule 4)
46-202Emergency power supply types: generator conforming to CSA C282 or central battery system. Automatic transfer equipment required (Rule 46-206)
46-302Unit equipment shall be mounted with the bottom at least 2 m above floor level, wherever practicable
46-304Unit equipment supply connections - typically connected to a receptacle on a normal lighting circuit in the area served, using flexible cord and attachment plug
46-400Exit signs - must be on a dedicated connection to a power supply; location requirements set by the Ontario Building Code

Monthly & Annual Testing Requirements

Test Frequency Duration
Functional test (verify lights turn on)MonthlyNo set duration
Full duration testAnnuallyFull design duration: 30 min, 1 h or 2 h
Generator transfer testMonthly60 min at 30 % or more load (CSA C282)

Frequently Asked Questions

How long must emergency lights stay on?

OBC 3.2.7.4 sets the duration by building type and occupancy: commonly 30 minutes, 1 hour, or 2 hours. CEC Section 46 governs the electrical emergency power supply and wiring. See our fire detector guide.

Where is emergency lighting required?

Exits, public corridors, principal routes (including service rooms) and assembly areas of 60+ occupants per OBC 3.2.7.3.

What are the testing requirements?

Monthly functional test, annual full-duration test; keep records per the Ontario Fire Code.

Related service

Electrical engineering

ETEM can review lighting objectives, controls and applicable life-safety requirements to define a coordinated design and approval path.